Sincerity Is Fundamental, Clients Is The First.

 

Strict Quality Control, Earnest Service Supply.

Home
Products
About Us
Factory Tour
Quality Control
Contact Us
Request A Quote
Home ProductsFault Passage Indicator

Epoxy Resin Insulated Overhead Fault Indicators For 6KV - 110KV Power Distribution Line

I'm Online Chat Now
Certification
China Beijing Tianyihongda Science & Technology Development Co., LTD certification
China Beijing Tianyihongda Science & Technology Development Co., LTD certification
Super friendly service, the Power Line Fault Indicator high quality as expected and very economy and environmental protection.

—— Bruce

This is the first time i do Underground Cable Fault Indicator business , after i received , it is work well. and now i want to order more.

—— Joseph

Epoxy Resin Insulated Overhead Fault Indicators For 6KV - 110KV Power Distribution Line

Epoxy Resin Insulated Overhead Fault Indicators For 6KV - 110KV Power Distribution Line
Epoxy Resin Insulated Overhead Fault Indicators For 6KV - 110KV Power Distribution Line Epoxy Resin Insulated Overhead Fault Indicators For 6KV - 110KV Power Distribution Line Epoxy Resin Insulated Overhead Fault Indicators For 6KV - 110KV Power Distribution Line Epoxy Resin Insulated Overhead Fault Indicators For 6KV - 110KV Power Distribution Line

Large Image :  Epoxy Resin Insulated Overhead Fault Indicators For 6KV - 110KV Power Distribution Line Get Best Price

Product Details:

Place of Origin: Beijing,China
Brand Name: Tianyihongda
Certification: type test report
Model Number: TYHD-AI1

Payment & Shipping Terms:

Minimum Order Quantity: 1set(3pcs)
Price: Negotiation
Packaging Details: 56*40*34cm,48 pcs /box ,standarad export box
Delivery Time: 3000 sets within 1 week
Payment Terms: L/C,, T/T, Western Union
Supply Ability: 3000sets per week
Detailed Product Description
Applied Inviroment: 6kv-110kv Power Distribution Line Function: Locate And Detect Short-circuit For Overhead Line
Usage: Locate And Detect Earth Fault For Overhead Line Alarm: Red Flag And Flashlight
High Light:

overhead fault indicators

,

remote fault indicator

Fault Passage Indicator is installed on the overhead power lines, is to detect the grounded and short circuit fault for overhead line. It will alarm during the day and flash during night to show the fault. According to the alarm information , the operator can locate the fault area quickly and find out the point of fault, which supply the best solution for the difficulty in finding fault area. This device can improve work efficiency, reduce power outage time and power restoration quickly.The installation and uninstalling way is very simple and convenient.
 
The parameters can be modified by client's requirement. default paramters is as following:
  • voltage applicable: 6kV-110KV
  • long withstand current: 630A
  • Power distribution frequency: 50HZ/60HZ
  • protection grade: IP68
  • line diameter applicable: 16mm2≤d≤400mm2
  • load current measurement range: 25A-630A, variable within 10s, line load minimum lasting time is 10s.
  • Earthed alarm value: 45A, can be adjustable before delivery.
  • Short-circuit alarm value: 120-150-220-320-400-900A, sudden changed value is self-adaptable. (can be customized by client before delivery)
  • Fault recognition time: 40ms-10s
  • Fault shock lasting time (surge suppression time) : 10s
  • Alarm response time: 0.02S≤T≤3S
  • Static power consumption: ≤20μA
  • reset time: 6,12,24,48 hours,can be defined by client oneself before delivery..
  • Ambient temperature: -40℃≤T≤+75℃
  • Alarm times: ≥2000 times
  • Led flash total hours: 10000 hours
  • Led Flash period for permanent fault: one flash every three second(can be customized by client before delivery,red flag is available if required)
  • Led Flash period for transient fault:two flash every forty(twelve) second (can be customized by client before delivery, red flag is available if required)
  • Visible angel: 360 degrees, 40 Lumens.
  • Battery life: 10 years, not changeable.
  • weight: ≤500g
  • Humidity: ≤95%
  • Size:74mm*112.5mm

applied range

  • Installed middle section and branch entrance on long line: can indicate line fault section and fault branch.
  • installed at substation exit:Can judge the fault is happened inside or outside the station .
  • installed user distribution and transformation high voltage line entrance:can judge if the fault is caused by users.
  • installed in the connection point between cable and overhead line:can judge if the fault happened in cable section.

 

 
There is type test report for it,  test items as following:
 

 

Type Test Items

 

1. appearance and structure 2.function 3. electrical device performance 4.low temperature performance 5.high temperature performance 6.alternating temperature humidity7.vibrationendurance 8.incline drop test 9. electrical device life 10. static electricity and elecro-discharge immunity test 11.radio frequency electromagnetic field radiated immunity test 12.surge impact immunity test 13. power frequency magnetic field immunity test. 14. Adjacent interference test 15.short-circuit withstand impact test 16. fire hazard test 17. power consumption test 18. protection grade test 19. gripping strength test of grip structure.